125
Ethernet Communications Section 7-3
Response Format (G9SP-series Controller to Standard PLC)
+0 Always C0 hex 1 byte
+1 Always 00 hex 1 byte
+2 Always 02 hex 1 byte
+3 Always 00 hex 1 byte
+4 FINS node address of Stan-
dard PLC
1 byte
+5 Unit number of Communica-
tions Unit in Standard PLC
1 byte
+6 Always 00 hex 1 byte
+7 FINS node address of G9SP-
series Controller
1 byte
+8
Always 00 hex 1 byte
+9 Service ID 1 byte
+10
Always 28 hex 1 byte
+11 Always 01 hex 1 byte
+12 End code (H) 2 bytes
+13 End code (L)
+14 Number of receive bytes (H) 2 bytes
+15 Number of receive bytes (L)
+16 Always 00 hex 1 byte
+17 Service code 1 byte
+18 Data 188 bytes
Parameter Description
FINS node
address of Stan-
dard PLC
The FINS node address that was set for the Standard PLC is
stored.
FINS node
address of
G9SP-series
Controller
The FINS node address that was set for the G9SP-series Control-
ler is stored.
Unit number of
Communications
Unit in Standard
PLC
Set the unit number that is set in the Communications Unit.
Service ID The service ID that was set in the command format is stored.
End code Normal command format (including an error response): 0000 hex
Error command format, in which case there is no subsequent
data: Not 0000 hex
Number of
receive bytes
Normal response: 00BE hex
Error response: 0004 hex
Service code Normal response: CB hex
Error response: 94 hex
Data Normal response: Refer to Transmission Data (G9SP-series Con-
troller to Standard PLC) in 7-1-3 Transmission/Reception Data
Error response: Two bytes of reserved data