190
Application Templates Appendix A
Timing Chart
Safety I/O Terminal Settings
Program
Precautions for Safe Use
Perform a function test every six months to detect contact welding failures on contactors.
It is the user's responsibility to make sure that the entire system complies with standards.
For safety reasons, two electrical switching elements and two mechanical actuators are
always necessary to detect electrical faults and mechanical faults.
Reset ON
Idle Run
More than
350 ms
More than
350 ms
S2 detects a
human body.
Robot arm goes to the side of the worker.
E-Stop pressed
E-Stop released
S2 detects a human body
and robot arm goes to the
side of the worker.
KM1, KM2
EDM feedback
Limit switch S4
Reset S5
Safety limit switch
S3
E-Stop S1
SLC1
S2
More than
350 ms
Input Terminals
Output Terminals