198
Application Templates Appendix A
Safety I/O Terminal Settings
Program
Precautions for Safe Use
Perform a function test every six months to detect contact welding failures on contactors.
It is the user's responsibility to make sure that the entire system complies with standards.
To detect electrical and mechanical failures, combine redundant semiconductor output con-
tacts with redundant mechanical output devices.
Wire the terminals correctly according to the wiring example. Connect the NO contacts on
the two-hand control switch to terminals Si0 and Si2 on the G9SP-series Controller and con-
nect the NC contacts to terminals Si1 and Si3. A malfunction will occur if the connections
are not correct.
Additional Information
The output will not turn ON if the simultaneous operation requirement of the two-hand con-
trol switch (i.e., that the operation inputs from both hands be completed within 500 ms) is not
met.
A two-hand control switch that is set as a safety input terminal operates as a single channel.
For dual-channel monitoring, use the Two-hand Control function block instead of safety input
terminals.