39
G9SP-series Controllers Section 2-1
Operation at Error Detection
The G9SP-series Controller performs the following actions if an error is
detected in the Safety Output terminals:
• The outputs to external devices are immediately made inactive regardless
of the status of the user program.
• The ERR indicator will flash red and the I/O indicator of the Safety Output
terminal where the error was detected will light red. In Dual Channel
Mode, indicator of the other output flashes red.
• The error is recorded in the error log.
• Operation continues.
Resetting Errors
All the following conditions must be met to reset errors that occur in the Safety
Outputs.
• The cause of the error must be removed.
• The output signal from the user application for the corresponding Safety
Output terminal to the output tag must be made inactive.