46
Expansion I/O Units Section 2-2
Output Specifications for Transistor Outputs (Sinking or Sourcing)
*1 If the ambient temperature is maintained below 50°C, up to 0.9 A/com-
mon can be used.
*2 The fuse cannot be replaced by the user. Replace the Unit if the fuse
breaks due to a short-circuit or overcurrent.
Precautions for Safe Use
Do not connect a load to an output terminal or apply a voltage in excess of the
maximum switching capacity.
Item Specification
CP1W-20EDT/20EDT1 CP1W-32ET/32ET1
Maximum switching
capacity
*1
24 VDC
+10%/-5%
0.3 A/output
4.5 to 30 VDC
0.3 A/output
0.9 A/common
1.8 A/Unit
0.9 A/common
7.2 A/Unit
Leakage current 0.1 mA max. 0.1 mA max.
Residual voltage 1.5 V max. 1.5 V max.
ON response time 0.1 ms max. 0.1 ms max.
OFF response time 1 ms max.
At 24 VDC +10%/ -5%, 5 to 300 mA
1 ms max.
At 24 VDC +10%/ -5%, 5 to 300 mA
Maximum number of
simultaneously ON
outputs
8 points (100% load) 24 points (75% load)
Fuse
*2
1 fuse/common
Circuit configuration
L
L
Output indicator
Internal
circuits
COM (-)
OUT
OUT
24 VDC/ 4.5 to 30 VDC
Sinking Outputs (CP1W-20EDT and CP1W-32ET)
L
L
Output indicator
Internal
circuits
COM (+)
OUT
OUT
Sourcing Outputs (CP1W-20EDT1 and CP1W-32ET1)
24 VDC/ 4.5 to 30 VDC
0.9
0.8
(A)
0
Ambient tem
erature
50 55 (˚C)
Total current per common