Page 122
To program the Flow 5 for Example 3 BS3680 Weir by using the Quick
Setup menu proceed as follows.
If required access the Program Mode
Key in the passcode 1997 and press ENTER
Using the ‘right’ arrow key go to the Quick Setup menu press ENTER and
as prompted, by the questions, select the relevant option and press ENTER.
Question
Option
PMD Type
3 = 3680 Weir
3680 Flumes
1 = Rectangular
Calculation
1 = Absolute
No. of Alarms
1 = 1 Alarm
Type Alarm 1
1 = High
Alarm No 1
3 = Set Relay 3
Xducer
1 = dB Mach3
Volume Units
1 = Litres
Time Units
1 = Per Minute
Measnt. Units
1 = metres
Empty Level
1.000 metres
Minimum Head
0.000 metres
Maximum Head
0.400 metres
Total Enable
1 = On
Totaliser (R)
1 =Yes
Total Multiplier
7 = 1000
App. Width (Dim A)
0.5 metres
Crest Width (Dim B)
0.3 metres
Crest Height (Dim C)
0.3 metres
Programming is now complete and the unit can now be returned to the run
mode, press CANCEL until Run Mode? Is displayed on the LCD press
ENTER, and the Flow 5 will return to Run Mode.
Note
If relay setpoints do not meet the exact requirements of the application, they
can be modified to suit by pressing ENTER when, “For More Options Hit
Enter”, is displayed, and entering new values to relay setpoints as required.
Alternatively, the relevant relay setpoint can be accessed either by the main
menu system or directly via parameter number and changed as necessary.