Page 173                                                                                                             
The  fourth  parameter,  and  the  fifth  parameter  for  each  relay  set  the 
pump “ON” and “OFF” points, which are entered in  Measurement units 
P104. For pump down the “ON” is set higher than “OFF”. For pump up 
then  “ON”  is  set  lower  than  “OFF”.  See  the  appropriate  pump  duty, 
function table (P212, 222, 232, 242, 252) for further information. 
P213, P223, P233, P243, P253 - Relay Setpoint 1 
This parameter determines the “ON” point of the pump. 
P214, P224, P234, P244, P254 - Relay Setpoint 2 
This parameter determines the “OFF” point for the pump. 
When a relay is being used for a pump by time function, then the sixth 
parameter will determine the maximum time the pump will be allowed to 
run before it is switched off and the next pump takes over.  
P215, P225, P235, P245, P255 - Relay Setpoint 3 
This parameter determines the Maximum Time the pump will be allowed to 
run before being switched “OFF” and is entered in minutes. 
The pump will switch off either at its “OFF” level Relay Setpoint 2 (P214, 
224, 234, 244, 254) or its Maximum Run Time Relay Setpoint 3 (P215, 
225, 235, 245, 255), whichever occurs first. 
P219, P229, P239, P249, P259 - Relay Max.Rate 
This parameter will allow a pump or general control relay to be switched 
at a pre-determined Rate of change of Level, irrespective of the “ON” level 
setpoint P213, 223, 233, 243, 253. Once a pump or general control relay has 
been switched “ON” by the pre-determined Rate of Change, it will remain 
energised until the level reaches  the “OFF” level setpoint P214, 224, 234, 
244, 254.  
Max. Rate is entered in Measurement Units (P104) per minute and can be 
entered  as  either  positive  (increasing  level)  or  negative  (decreasing level) 
values.