Page 193
P706 Volume Units
Select the Volume Units to be used to display and calculate the flow rate
from the options below:
Option
Description
1= Litres (Default)
Flow will be calculated and displayed in Litres
2= Cubic metres
Flow will be calculated and displayed in Metres
3
3= Cubic feet
Flow will be calculated and displayed in Feet
3
4= UK Gallons
Flow will be calculated and displayed in UK Galls.
5= US Gallons
Flow will be calculated and displayed in US Galls.
6 = Mil. USG
Flow will be calculated and displayed in Millions
of US Galls.
P707 Time Units
Select the Time Units to be used with the Volume Units to determine the
desired flow rate from the options below:
Option
Description
1= per Second (Default)
Flowrate will be calculated and displayed in
Volume units/Second
2= per Minute
Flowrate will be calculated and displayed in
Volume units/Minute
3= per Hour
Flowrate will be calculated and displayed in
Volume units/Hour
4= per Day
Flowrate will be calculated and displayed in
Volume units/Day
P708 Flow Decimal
This parameter determines the number of decimal places in the flow rate
reading during run mode. It can be set between 1 and 3. Default = 2
P709 Flow Cut Off
This parameter is used to select the minimum flow, in a % of flow rate,
which is to be totalised. Enter values in % of maximum flow. Default = 5%