Page 49
The default values used for determining the relay setpoints, when setting
Alarm and Control relays, via the Quick Setup menu are entered as a % of
span and are as follows.
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Cntl. Down
One
Control 1
80%
20%
Cntl. Down
Two
Control 1
Control 2
80%
70%
20%
20%
Cntl. Down
Three
Control 1
Control 2
Control 3
80%
70%
60%
20%
20%
20%
Cntl. Down
Four
Control 1
Control 2
Control 3
Control 4
80%
70%
60%
50%
20%
20%
20%
20%
Cntl. Down
Five
Control 1
Control 2
Control 3
Control 4
Control 5
80%
70%
60%
50%
40%
20%
20%
20%
20%
20%
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Cntl. Up
One
Control 1
20%
80%
Cntl. Up
Two
Control 1
Control 2
20%
30%
80%
80%
Cntl. Up
Three
Control 1
Control 2
Control 3
20%
30%
40%
80%
80%
80%
Cntl. Up
Four
Control 1
Control 2
Control 3
Control 4
20%
30%
40%
50%
80%
80%
80%
80%
Cntl. Up
Five
Control 1
Control 2
Control 3
Control 4
Control 5
20%
30%
40%
50%
60%
80%
80%
80%
80%
80%

Table of Contents