Page 75
Application
Number of
Pumps
Pump
Number
On
Setpoint
Off
Setpoint
Pump Up
One
Pump 1
50%
80%
Pump Up
Two
Pump 1
Pump 2
50%
30%
80%
80%
Pump Up
Three
Pump 1
Pump 2
Pump 3
50%
40%
30%
80%
80%
80%
Pump Up
Four
Pump 1
Pump 2
Pump 3
Pump 4
60%
50%
40%
30%
80%
80%
80%
80%
Pump Up
Five
Pump 1
Pump 2
Pump 3
Pump 4
Pump 5
60%
50%
40%
30%
25%
80%
80%
80%
80%
80%
Application
Number of
Cntl Relays
Cntl Relay
Number
On
Setpoint
Off
Setpoint
Level
Cntl. Down
One
Control 1
80%
20%
Level
Cntl. Down
Two
Control 1
Control 2
80%
70%
20%
20%
Level
Cntl. Down
Three
Control 1
Control 2
Control 3
80%
70%
60%
20%
20%
20%
Level
Cntl. Down
Four
Control 1
Control 2
Control 3
Control 4
80%
70%
60%
50%
20%
20%
20%
20%
Level
Cntl. Down
Five
Control 1
Control 2
Control 3
Control 4
Control 5
80%
70%
60%
50%
40%
20%
20%
20%
20%
20%

Table of Contents