DURADRIVE Drive Controllers DURADRIVE HDC01.1 Drive Controller 4-63
DOK-DURADR-HDC01.1****-PR02-EN-P
XE1, Protective conductor connections for mains
Technical description of connector
See page 4-21: "A look at the drive controller and connector
designations".
Type No. of pins Design
screw-in connection 1 screw-in connection for
ring terminals M5
Fig. 4-113: Design
min. tightening torque
[Nm]
max. tightening torque
[Nm]
2.5 3.0
Fig. 4-114: Tightening torque
Cross section
single wire
[mm²]
Max. connectable
cross section
in mm²
Max. cross section
in AWG
gauge no.:
-- 25 --
Fig. 4-115: Connection cross section
XE1, protective conductor connection for mains
DANGER
Personal danger caused by large leakage
current!
The DURADRIVE drive controller is equipped with
an integrated power line filter. In order to prevent
danger, the connection cross section of the ground
wire connector XE1, in principle, must be at least
10 mm² (EN 50178/1998, section 5.3.2.1).
Illustration
Design
Tightening torque
Connection cross section