Only when there is a low to high trigger at Trg pin, the Memory
Read block will be activated and xLogic CPU will read some data (bit
or short) to set pre-configured register from the file in the SD card
of ELC-MEMORY module. Each trigger, only write once.
Reset the Memory Read block and set the output to 0 via the R
(Reset) input.
Reset has priority over Trg
Q switches on only after the Read function had been executed
correctly, provided.
Description of Memory write block’s property dialog box:
1. File name
The name of the file which you want to access is stored in the mini-SD card of the ELC-MEMORY module.
2. Record Title
Below is an example in the “OUTPUT.TXT”
3. Data Type:
Two options available: Option A. BIT (0 or 1, this is used to be set the status of Q or F )
Option B . WORD (this is used to be set the value of AQ or AF)
4. Record Index:
Here is used to set which line the CPU will access via this Memory Read block