30
2.
Connecting xLogic is shown as in the following figures:
* DC type digital inputs
AC Type
DC Type
Signal status 0
Input current
<40VAC
<0.03mA
<5VDC
<0.1mA
Signal status 1
Input current
>79 VAC
Typical 0.06
0.24mA
>10VDC
Typical 0.3mA
Analogue input
NO
AI1-AI4(0-10V DC)(PR-6,PR-12)
Note:
1. For PR-6DC-DA-R, PR-12DC-DA ,PR-14DC-DA,
PR-18DC-DA ,PR-24DC-DA Series and versions. That can receive analog
input. They can be set to analog input or digital input as either may be
used in the program. They will be recognized as analog inputs when the
input terminal is connected with an analog function block, and they will be
recognized as switching inputs when the input terminal is not connected
with an analog function block.
2. The analog inputs require DC 0V ~ +10V voltage signals. These are
divided equally in 0.01V increments. In programming, all the block
parameters related to the analog inputs are based on the minimum
increment of 0.01V.
3. They can be recognized as switching input when the input voltage is more
than 10.0V and cannot be recognized as an analog input.
4. For the switching input off, when the switch status changes from 0 to 1,
the time of Status 1 must be greater than 50ms, and when the switch status
changes from 1 to 0, the time of Status 0 also must be greater than 50ms.