8. PARAMETER DESCRIPTION
IMR02C15-E4
8-40
Minimum ON/OFF time of proportioning cycle
[cool-side]
Factory default setting:
The screen is displayed.
This is the Minimum ON/OFF time of the time proportioning cycle [cool-side].
Data range Factory set value
0 to 1000 ms 0
This parameter is displayed when in Heat/Cool PID control.
Minimum ON/OFF time of proportioning cycle [cool-side] displays when
relay contact output, voltage pulse output, triac output or open collector
output is specified to control output 2 (OUT2).
Minimum ON/OFF time of proportioning cycle [cool-side] is not
displayed when the block selection at F08 [S.F08] (P. 8-83) is set to
“1: No display” in the Engineering mode.
Related parameters
Parameter setting mode:
Proportional cycle time [cool-side] (P. 8-39)
Engineering mode:
Minimum ON/OFF time of proportioning cycle [cool-side] (P. 8-82)
Mt