6. OPERATIONS OF THE BASIC FUNCTIONS
IMR02C15-E4
6-37
îš„ Hiding the parameters of the Parameter setting mode
Setting example: Setting the PV bias screen and PV digital filter screen to no display
The PV bias and PV digital filter screens are set by the F09 block selection (no
display) of Engineering mode.
1. In PV/SV monitor, press the key for 4 seconds or more while pressing the key.
The display goes to the Engineering mode.
2. Press the key until Function block 09 (F09) screen is displayed.
3. Press the key until F09 block selection (no display) screen is displayed.
4. Press the key to change to 1.
Set value and description
0: Display
1: No display
5. Press the key to store the new value. The display goes to the next parameter.
After a new value is displayed on the display by using and keys, if no key operation is
performed within 1 minute without pressing key, this instrument returns to the Monitor
display mode and the set value will not be changed.
SET
R/S
SET
S
F09
0001
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
SET
F09.
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
Function block 09 (F09)
28
200
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
PV/SV monitor
F00.
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
Engineering mode
Function block 00 (F00)
(4 seconds or more)
SET
R/S
+
F00.
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
F09.
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
Engineering mode
Function block 09 (F09)
SET
S
F09
0000
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
S
F09
0001
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
F09.
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
S
F09
0000
SV1
OUT1
OUT
T
DO1 DO
MAN
STOP
DO3
DO4
F09 block selection (no display)
SET
SET