10. SPECIFICATIONS
IMR02C15-E4
10-5
îš„ Output
Number of output: Up to 6 points (RB100: Up to 4 points)
Output type: Relay contact output (1)
Contact type: 1a contact
Contact rating (Resistive load): 250 V AC
3 A, 30 V DC
1 A
Electrical life: 100,000 times or more (Rated load)
Mechanical life: 20 million times or more
(Switching: 360 times/min [no-load])
Relay contact output (2)
Contact type: 1a contact
Contact rating (Resistive load): 250 V AC
1 A, 30 V DC
0.5 A
Electrical life: 150,000 times or more (Rated load)
Mechanical life: 20 million times or more
(Switching: 360 times/min [no-load])
Voltage pulse output:
Output voltage (Rating): 0/12 V DC
ON voltage: 10 V to 13 V (at 20 mA)
OFF voltage: 0.5 V or less
Allowable load resistance: 600 Ω or more (20 mA or less)
Not using OUT2: 40 mA or less
Current output:
Output current (Rating): 0 to 20 mA DC, 4 to 20 mA DC
Output range: 0 to 21 mA DC, 1 to 21 mA DC
Allowable load resistance: 500 Ω or less
Output impedance: 1 MΩ or more
Voltage output:
Output voltage (Rating): 0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC
Output range: −0.25 to +5.25 V DC, 0.8 to 5.2 V DC,
−0.5 to +10.5 V DC
Allowable load resistance: 1 kΩ or more
Output impedance: 0.1 Ω or less
Triac output:
Output method: AC output (Zero-cross method)
Allowable load current: 0.5 A (Ambient temperature 40 °C or less)
Ambient temperature 50 °C: 0.3 A
Load voltage: 75 to 250 V AC
Minimum load current: 30 mA
ON voltage: 1.6 V or less (at maximum load current)
Open collector output:
Output method: Sink type
Allowable load current: 100 mA
Load voltage: 30 V DC or less
Minimum load current: 0.5 mA
ON voltage: 2 V or less (at maximum load current)
Leakage current at OFF: 0.1 mA or less