10. SPECIFICATIONS
IMR02C15-E4
10-17
Self-diagnostic function
Control stop (Error number is displayed [Operation: Possible]):
Adjustment data error (Err 1)
Data back-up error (Err 2)
A/D conversion error (Err 4)
Temperature compensation error (Err 4)
Action stop (Error number is not displayed [Operation: Impossible]):
Power supply voltage is abnormal
Watchdog timer
Power
Power supply voltage: 100 to 240 V AC type:
90 to 264 V AC [Including power supply voltage variation], 50/60 Hz,
(Rating 100 to 240 V AC)
Frequency variation: 50 Hz±10 %, 60 Hz±10 %
24 V AC type:
21.6 to 26.4 V AC [Including power supply voltage variation], 50/60 Hz,
(Rating 24 V AC)
Frequency variation: 50 Hz±10 %, 60 Hz±10 %
24 V DC type:
21.6 to 26.4 V DC [Including power supply voltage variation]
(Rating 24 V DC)
Power consumption (at maximum load):
RB100: 5.5 VA max. (at 100 V AC)
8.5 VA max. (at 240 V AC)
4.7 VA max. (at 24 V AC)
108 mA max. (at 24 V DC)
RB400/500: 6.0 VA max. (at 100 V AC)
8.7 VA max. (at 240 V AC)
5.8 VA max. (at 24 V AC)
141 mA max. (at 24 V DC)
RB700: 6.0 VA max. (at 100 V AC)
8.7 VA max. (at 240 V AC)
5.8 VA max. (at 24 V AC)
147 mA max. (at 24 V DC)
RB900: 6.2 VA max. (at 100 V AC)
9.0 VA max. (at 240 V AC)
6.0 VA max. (at 24 V AC)
147 mA max. (at 24 V DC)
Rush current: 5.6 A or less (at 100 V AC)
13.3 A or less (at 240 V AC)
16.3 A or less (at 24 V AC)
11.5 A or less (at 24 V DC)