146 Rockwell Automation Publication 1734-UM013J-EN-P - July 2014
Chapter 8 Replacing POINTGuard I/O Modules
1. Remove the old I/O module and install the new module.
2. Right-click your POINT Guard I/O module and choose Properties.
3. Click the Safety tab.
4. Click Reset Ownership.
5. Click OK.
6. Follow your company-prescribed procedures to functionally test the
replaced I/O module and system and to authorize the system for use.
If then
the module is in out-of-box condition go to step 6
.
No action is needed for the GuardLogix controller to take
ownership of the module.
an SNN mismatch error occurs go to the next step to reset the module to out-of-box condition.