Rockwell Automation Publication 1734-UM013J-EN-P - July 2014 93
Configure the Module in a GuardLogix Controller System Chapter 5
c. From the Electronic Keying pull-down menu, choose the appropriate
keying method for the input module.
d. From the Configured By pull-down menu, choose the appropriate
method by which this module is configured.
e. From the Input Data pull-down menu, choose Safety.
f. From the Output Data pull-down menu, choose from the following.
g. From the Process Data pull-down menu, choose from the following.
h. From the Data Format pull-down menu, use the default ‘Integer.
5. Click OK to return to the Module Properties dialog box.
6. Click OK again to apply your changes.
The I/O Configuration tree displays the 1734-IE4S module.
Choose Description
Exact Match All of the parameters must match or the inserted module rejects a connection to
the controller.
Compatible
Module
Allows an I/O module to determine whether it can emulate the module defined in
the configuration sent from the controller.
Choose Description
This Controller This selection directs the controller to configure the Inputs.
External Means This selection directs the controller to establish a safety input connection only,
and the controller will not configure the module.
Choose Description
None An output tag is not generated.
Safety-Tachometer This option is available when the Configured By selection is This Controller. The
output tag contains data members for safety output data needed for
Tachometer mode. If you are using Tachometer mode, you must choose this
setting; otherwise, you will not be able to configure other Tachometer
parameters.
Choose Description
Status The input tag contains safety analog input data from the module.
Status - Alarms These tags are created for the target module:
Safety data for individual process alarms
Safety data for safety analog inputs from the module
Status - Alarms - Faults These tags are created for the target module:
Safety data for individual process alarms
Safety data for faults
Safety data for safety analog inputs from the module

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley POINT Guard and is the answer not in the manual?

Rockwell Automation Allen-Bradley POINT Guard Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley POINT Guard
CategoryI/O Systems
LanguageEnglish

Related product manuals