Rockwell Automation Publication 750-TG100B-EN-P - June 2019 129
Frame 7 Components Chapter 6
9. Remove the two M8 x 30 mm torx screws that secure the circuit breaker
AC output flexible bus bars to the AC input terminals on the LCL filter
and remove the bus bars.
10. Remove the two M8 x 30 mm torx screws that secure each of the LCL
filter AC output flexible bus bars to the AC input terminals on the line
side converter power module and remove the bus bars.
9,
10
M8 x 30 mm
T40
19.8 N•m (175 lb•in)
9