Rockwell Automation Publication 750-TG100B-EN-P - June 2019 91
Frame 6 Components Chapter 5
LCL Filter Capacitor
Replacement
Replace an LCL filter capacitor with kit catalog number: SK-RM-LCLCP4-F6
(400…690V).
Remove the LCL Filter Capacitor
Follow these steps to remove the LCL filter capacitor.
1. Review the Product Advisories on page 14
.
2. Remove power from the system. See Remove Power from the System on
page 15
.
3. Remove the cover from the chassis. See Remove the Cover on page 76
.
4. Remove the M12 hex nut that secures the capacitor to the bracket.
5. Cut the cable ties that secures the capacitor to the bracket and discard the
cable ties.
4
M12
19 mm
9.0 N•m (80 lb•in)
5