Factory settings parameters
P100011294 E 133
Parameter Description Factory settings New
P-41 Set wall temperature correction of wireless room thermo-
stat.
0 K
P-42 Set floor temperature correction of wireless room thermo-
stat with integrated IR-sensor.
0
P-43 Set maximum floor temperature of wireless room thermo-
stat with integrated IR-sensor.
35 °C
P-44 Set reduction of room temperature for "Eco" function. 3 K
P-45 Activate or deactivate cooling lock and/or bypass, e.g. for a
heat pump.
0
P-46 Activate or deactivate "setpoint sharing within one zone" 0: deactivated
P-47 Activate or deactivate lock for public spaces or hotels. 0: deactivated
P-48 Activate or deactivate master function of a wireless room
thermostat.
0: deactivated
Parameter Description Factory settings New
P-51 Set priorities for change-over of heating/cooling and config-
ure output for heating/cooling or burner start.
0
P-52 Activate or deactivate "optimized time program". 0: deactivated
P-53 Set wireless communication between the wireless connec-
tion modules.
0: Wireless signal
activated
Parameter Description Factory settings New
P-61 Configure Eco or N/R input. 0
P-62 Configure C/O in-/TB-input. 2
P-63 Select control of pump "local" or "Master-wireless connec-
tion module" (only with activated communication between
wireless connection modules).
0
P-64 Select NC or NO function of thermal actuators. 0: NC
P-65 Select control algorithm. 0: On/Off
P-66 Activate or deactivate function "optimized actuator control". 0: deactivated
P-67 Select controlled first start-up of floor heating. 0: deactivated