Parameter descriptions
94 P100011294 E
9.3.7 P-60 "Control parameters"
Parameter Description
P-61 Configure Eco or N/R input.
With the Eco-input it is possible to override the actual mode of operation of all wire-
less room thermostats with an additional main switch or SMS-modem. Depending
on the selected option this function can either switch between "normal" and "re-
duced" or between "normal" and "frost protection (off)".
If the Eco-input is activated, then the display shows the symbol
.
Factory settings: Option "0"
Options:
0: N/R-input is inactive. If at the wireless room thermostats a time program is
selected, then this time program has priority.
1: The Eco-input has the highest priority, switches to "reduced".
Eco-input active: time program wireless room thermostat deactivated,
mode of operation and setpoint can be changed.
Eco-input inactive: all functions of wireless room thermostat available,
including time program.
2: The Eco-input has the highest priority, switches to "reduced".
Eco-input active: time program wireless room thermostat deactivated,
mode of operation and setpoint can be changed.
Eco-input inactive: all functions of wireless room thermostat available,
excluding time program. Symbol
is fix.
3: The Eco-input has the highest priority, switches to "frost protection".
Eco-input active: time program wireless room thermostat deactivated,
mode of operation and setpoint can be changed.
Eco-input inactive: all functions of wireless room thermostat available,
including time program. Symbol
4: The Eco-input has the highest priority, switches to "frost protection".
Eco-input active: time program wireless room thermostat deactivated,
mode of operation and setpoint can be changed.
Eco-input inactive: all functions of wireless room thermostat available,
excluding time program. Symbol
is fix.
Operation
Press sensor button
. The display shows 0.
Press sensor button
or , to select option 0, 1, 2, 3 or 4.
Select one of the following options:
Press sensor button , to save the changed settings. The display shows the
next parameter P-62.
Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.