Parameter descriptions
84 P100011294 E
9.3.4 P-30 "Parameters for all wireless room thermostats"
Any change of the following parameters will be transmitted to all wireless room
thermostats that are assigned to the wireless connection module.
It can take up to 10 minutes before all wireless room thermostats that are in
stand-by-mode have received the transmitted data. If the wireless room ther-
mostat is manually changed from stand-by-mode to operation-mode, the new
data is immediately collected from the wireless connection module.
Parameter Description
P-31 Set increment for room temperature setpoint adjustment.
Factory settings: option "0"
Options:
0: 0.5 K (1 F)
1: 0.1 K (0.2 F)
2: 0.2 K (0.5 F)
Operation
Press sensor button . The display shows 0.
Press sensor button
or , to select option 1 or 2.
Select one of the following options:
Press sensor button , to save the changed settings. The display shows the
next parameter P-32.
Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.
P-32 Set temperature for frost protection function.
The frost protection function will be activated as soon as the measured room tem-
perature is below the set frost protection temperature.
Factory settings: 8.0 °C
Setting range: 3…13 °C
Operation
Press sensor button . The display shows 8.0.
Press sensor button
or , to change the value.
Select one of the following options:
Press sensor button , to save the changed settings. The display shows the
next parameter P-33.
Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.