User Manual Roth EnergyLogic Touchline/Wireless
Parameter descriptions
P100011294 E 87
Parameter Description
P-38 Deactivate or activate automatic time settings.
NOTE
Only for LAN- versions with active internet connection: The wireless connection
module can get the current time from the internet to keep the date and time up to
date.
● Factory settings: Option "0" for wireless connection modules with LAN-interface
● Options:
– 0: activate
– 1: deactivate
Operation
► Press the sensor button
. The display shows 1.
► Press the sensor button
or to select the option 0 or 1.
► Perform one of the following steps:
– Press the sensor button to save your change. The display shows the next
parameter P-31.
– Press the sensor button to cancel the process. The display shows the se-
lected parameter again.
► Press the sensor button
. The display shows P-30.
Table 17: Service menu –P-30 "Parameters for all wireless room thermostats"
9.3.5 P-40 "Parameters for individual wireless room thermostats"
Parameter Description
P-41 Set wall temperature correction of wireless room thermostat.
The compensated temperature will be shown at the display as actual value.
● Factory settings: 0 K
● Setting range: –3…+3 K
● Increment: 0.1 K
Operation
► Press sensor button
. The display shows 0.
► Press sensor button
or , to change the value.
► Select one of the following options:
– Press sensor button , to save the changed settings. The display shows the
next parameter P-42.
– Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.