User Manual Roth EnergyLogic Touchline/Wireless
Parameter descriptions
88 P100011294 E
Parameter Description
P-42
IR
Set floor temperature correction of wireless room thermostat with integrated IR-
sensor.
Factory settings: Option "0"
Options:
0, standard setting: suitable for wood floors
1, average compensation: suitable for plastic floorings
2, high compensation: suitable for ceramic floors
NOTE
The specified settings apply at a room temperature of 22 °C.
For dark floorings or if the room temperature is at approx. 25 °C, you need to
switch up the compensation factor one level for all floors except for ceramic
floors.
No obstacles such as carpets, floorings or furniture must be placed in the meas-
uring range of the IR sensor.
Glossy floorings, e.g. due to sun irradiation, may cause measuring errors at the
IR sensor.
Operation
Press sensor button
. The display shows 0.
Press sensor button
or , to select option 1 or 2.
Select one of the following options:
Press sensor button , to save the changed settings. The display shows the
next parameter P-43.
Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.
P-43
IR
Set maximum floor temperature of wireless room thermostat with integrated IR-
sensor.
This parameter avoids that the floor temperature exceeds a maximum temperature
level.
ATTENTION
This function is not designed as a safety limiter. Therefore any liability for damages
to the floor construction or plant components is expressly excluded. If a safety tem-
perature limiter function is required then this has to be provided by an external
hardwired safety temperature limiter (STB).
Factory settings: 35 °C
Setting range: 26…35 °C
Increment: 1 K
Operation
Press sensor button . The display shows 35.
Press sensor button
or , to change the value.
Select one of the following options:
Press sensor button , to save the changed settings. The display shows the
next parameter P-44.
Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.