Parameter descriptions
P100011294 E 89
Parameter Description
P-44 Set reduction of room temperature for "Eco" function.
The frost protection function has a higher priority than the Eco function. See pa-
rameter description P-32, page 84.
Independently of the set value, the reduced temperature cannot lower than 11 °C
and not higher than 21 °C. This limitation will be selected automatically.
● Factory settings: 3 K below the actual setpoint.
● Setting range: 0…+10 K
● Step size: 1 K
Operation
► Press sensor button
. The display shows 3.
► Press sensor button
or , to change the value.
► Select one of the following options:
– Press sensor button , to save the changed settings. The display shows the
next parameter P-45.
– Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.
P-45 Activate or deactivate cooling lock and/or by-pass, e.g. for a heat pump.
NOTE
● For applications that can lead to high temperatures, like solar heating, we strong-
ly advise not to activate the function "By-pass heating" as the radio channel of
the "by-pass heating" is not closed by the alarm of the TB-input.
● When a heat pump is not equipped with a pressure overload by-pass, we advise
to configure one or more heating loops (depending on the minimum load re-
quirements), as by-pass.
● Factory settings: Option "0"
● Options:
The function is only activated for the channel(s) that are assigned to the wireless
room thermostat.
– 0: By-pass inactive, cooling lock inactive
– 1: By-pass "heating" active, cooling lock inactive
– 2: By-pass "cooling" active, cooling lock inactive
– 3: By-pass "heating" and by-pass "cooling" active, cooling lock inactive
– 4: By-pass inactive, cooling lock active
– 5: By-pass "heating" active, cooling lock active
Operation
► Press sensor button . The display shows 0.
► Press sensor button
or , to select option 1, 2, 3, 4 or 5.
► Select one of the following options:
– Press sensor button , to save the changed settings. The display shows the
next parameter P-46.
– Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.