User Manual Roth EnergyLogic Touchline/Wireless
Parameter descriptions
P100011294 E 85
Parameter Description
P-33
Set unit for temperature.
● Factory settings: Option "0"
● Options:
– 0: °C
– 1: F
Operation
► Press sensor button . The display shows 0.
► Press sensor button
or , to select option 1.
► Select one of the following options:
– Press sensor button , to save the changed settings. The display shows the
next parameter P-34.
– Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.
P-34 Set dead-zone for change-over between heating and cooling.
The dead-zone will be applied by the wireless connection module as soon as the
mode of operation changes over from heating to cooling and visa versa. The value
of the dead-zone will be added to the setpoint "heating". The dead-zone is incorpo-
rated in the displayed room temperature setpoint.
Calculation: Setpoint "cooling" = Setpoint "heating" + dead-zone
Example: Setpoint "heating" = 21°C (shown setpoint during heating)
Dead-zone = 2 K,
Result: Setpoint "cooling" = 21 + 2 = 23°C. (shown setpoint during cooling)
NOTE
The value for the "dead-zone" may only be changed if the mode of operation is set
at "heating". If this value is set during "cooling", the value will be doubled!
● Factory settings: Option "0"
● Options:
– 0: 2 K
– 1: 4 K
– 2: 6 K
– 3: 0 K, dead-zone deactivated
Operation
► Press sensor button . The display shows 0.
► Press sensor button or , to select option 1, 2, or 3.
► Select one of the following options:
– Press sensor button , to save the changed settings. The display shows the
next parameter P-35.
– Press sensor button , to interrupt the procedure. The display shows the se-
lected parameter.