SATEL INTEGRA 93
signaling stops after the maximum duration of acoustic signaling elapses, even if the
control output is still active. The optical signaling is active as long as the output is active.
ASP-205 / ASP-215 – both outputs control acoustic and optical signaling. Thus two different,
independently triggered ways of signaling can be configured. As a result, the outputs can
separately control the optical and acoustic signaling or trigger other signaling for different
alarms (e.g. burglary and fire). The command to start the signaling is sent to the siren only
during the response time. Therefore, the cut-off time for the control panel outputs which
control the siren must be longer than the response period. It is recommended that cut-off
time correspond to maximum duration of signaling programmed for the siren. The signaling
stops after the maximum duration of signaling elapses, even if the control output is still
active.
The zones to which the wireless siren is assigned are activated if a siren power supply
trouble occurs (select the appropriate reaction type for the zones):
ASP-105 – first zone: low battery; second zone: 12 V DC power loss.
ASP-205 / ASP-215 – both zones: low battery.
If the siren tamper is to trigger tamper alarm, program the zone as 2EOL/NC or 2EOL/NO.
The tamper information is sent immediately, while the trouble information – during the
response time.
Tamper alarm on opening the tamper switch in the siren:
ASP-105 – lasts for the maximum time of acoustic signaling programmed for the siren (sound
type selected during programming and optical signaling),
ASP-205 / ASP-215 – lasts 3 minutes (sound type 1 and optical signaling).
After starting the SERVICE MODE or TEST MODE and for 40 seconds after power-up, the
signaling in the siren is blocked. It enables installation work to be carried out. Opening
the tamper switch will not trigger loud signaling, but information on tamper will be sent
(when in service mode, the control panel will not signal the tamper alarms). The
command to block/unblock the signaling connected with starting / ending the test
mode or the service mode is sent during the response time.
9.3.3 Wireless expanders of hardwired zones and outputs
The wireless expander of hardwired zones and outputs (ACX-200 / ACX-201 / ACX-210 /
ACX-220) takes up 4 zones and 4 outputs in the system. You can configure the alarm system
zone/output to which expander zone/output is assigned in much the same way as hardwired
zones/outputs. You should remember however that sensitivity of the expander zones may be
different from that programmed in the control panel:
– from 20 ms to 140 ms – the same as the value programmed in the control panel,
– above 140 ms – only some values are available: 400 ms, 500 ms, 700 ms, etc. every
200 ms (the programmed value is rounded up to that supported by the expander).
The EN50131-3 standard requires that zones must react to signals lasting more than
400 ms. Therefore, select 400 ms when programming sensitivity of the alarm zones.
Information on the state of zones and commands to change the state of outputs are sent
immediately. Zone settings are sent during the response time (in one period, data relating to
configuration of one zone are sent to the expander module, i.e. sending the information on
settings of four zones require four response periods).
If communication with the control panel is lost, all previously activated outputs will be
deactivated after 20 response periods.
Additionally, the ACX-201 expander module sends information about:
• status of AUX1 and AUX2 power supply outputs – information on overload is sent when
the AUX1 or AUX2 output load exceeds 0.5 A.