SATEL INTEGRA 87
can work within each other's operating range (12 seconds – up to 150, 24 seconds – up to
300, 36 seconds – up to 450). Beyond the response period, information about tampers of
devices and violations of detectors operating in active mode are sent to the control panel.
The response period has an effect on the level of energy consumption by the wireless
devices. The less often communication between the control panel and the wireless devices
takes place, the lower energy consumption and the longer battery life are.
In the case of the AMD-103 detector, no communication takes place during polling.
Higher sensitivity for jamming detection – if this option is enabled, the sensitivity of
detection of radio communication jamming is boosted.
Synchronize – this function starts the procedure of synchronization, i.e. checking for
presence of other ABAX 2 / ABAX wireless systems working within the control panel
operating range. The control panel will synchronize the response period so that the radio
transmissions of some systems should not be mutually jammed. Synchronization is
performed automatically upon starting the control panel and after each operation of
adding/removing devices supported by it.
Test mode – to carry out diagnostics / service work, you can start the test mode in the ABAX
system. When the system is running in the test mode:
– detector LEDs are enabled,
– tamper signaling in the sirens is blocked.
The command to start/end the test mode is sent during polling, i.e. with delay whose
duration depends on the frequency of polling. The test mode will be disabled automatically
30 minutes after:
– starting the test mode from the DLOADX program (the 30-minute period is running from
the moment of exiting the system ABAX settings),
– exiting the service mode in the control panel.
According to requirements of the EN50131 standard, the level of radio signals sent by
wireless devices is reduced during the test mode operation.
For the AMD-103 detector, entering the test mode remotely is not possible.
9.2 Parameters and options of wireless devices
Filter – the number of consecutive response periods, during which communication with the
device failed to be established, for the loss of communication with the device to be
reported. Values from the 0 to 50 range can be entered. Entering the digit 0 will disable
control of the device presence in the system.
In the case of the AMD-103 magnetic contact, the presence check is performed in
a different way than for the other ABAX 2 / ABAX devices. If the value programmed for
the FILTER parameter differs from 0, the lack of presence will be reported if no
transmission from the AMD-103 magnetic contact is received within one hour.
Always active – the option is available for the most of wireless detectors. If enabled, the
detector is permanently switched over to the active mode (see “Wireless detectors” p. 92).
The AMD-103 detector and the wireless detectors assigned to 24-h zones are always
in the active mode, therefore the ALWAYS ACTIVE option does not have to be enabled
for them.