F12 Event Class V-MAX H3
Range: WARNING 2
WARNING 1
IGNORE
ALARM
Default:
WARNING 2
Block G : Filters
I = feed rate V = belt speed
G01 I Display
Range: 0.0...600.0 s Default: 3.0 s
Feed rate display
G02 I Analog output
Range: 0.0...600.0 s Default: 3.0 s
Feed rate analog output
G03 Q Display
Range: 0.0...600.0 s Default: 3.0 s
Belt load display
Q = belt load
G04 V Display
Range: 0.0...600.0 s Default: 3.0 s
Belt speed display
G05 L/C Filter
Range: 1.0...600.0s Default: 1.0 s
Holds for all
functions and displays depending on belt
load.
G06 Afterfl. Time
Range: 0.0...2000.0 s Default: 3.0 s
Determines the time totalization goes on after turn-off
of feeder.
All filters are of the 1st order type
(exponential), i.e. after abrupt
change of signal, approx. 2/3
of the limit value are reached
after the set time.
Longer times stabilize display
but reduce update rate.