I07 Belt Empty
Range: NO
YES
Default: NO
NO : Batching without belt clearance.
Stop of conveyor belt aborts batch.
YES : Batching with belt clearance.
Stop of prefeeder aborts batch.
(Prefeeder Active M 01 = YES)
I08 Batch > Setp. B4
Range: IGNORE
WARNING1
WARNING 2
ALARM
Default: IGNORE
Batch actual value exceeds setpoint by tolerance I 04.
Message B4 is output.
After acknowledgement (also ALARM messages),
monitoring of current batch cuts off.
I09 Batch Source
Range: OP
FB Default: OP
OP : Batch setpoint, batch number and make-up
setpoint are preset from the INTECONT
keyboard.
FB : Above values are set via fieldbus interface.
0837
VBW INTECONT PLUS
Parameterization
BV-H2214 GB 62
Technische
Redaktion PDE-RD
Transmission to third parties and reproduction of
this documentation are not permitted. Schenck
Process GmbH reserves all rights of ownership
and copyrights.