Block O: Events
O01 Power Failure E1
Range: ALARM
WARNING 1
WARNING 2
IGNORE
Default: ALARM
O02 Memory Error S1
ALARM (S01) No changes possible.
Feeder is no longer operable.
O03 Tacho Input C2
Range: ALARM
WARNING 1
WARNING 2
Default: ALARM
Input frequency exceeds 2700 Hz.
Monitoring starts 10 s after power-up.
Prerequisite: B 03 = YES
O04 Namur Err. Tacho E2
Range: ALARM
WARNING 1
WARNING 2
IGNORE
Default: ALARM
Cable breakage or short-circuit.
Prerequisite: B 03 = YES
Namur errors reset internal speed value to 0.
Frequency display (service value) is still active.
O05 Namur Err Belt E3
Range: WARNING 1
ALARM
IGNORE
Default: WARNING 1
Short-circuit or breakage of belt circuit sensor cable
(BIC).
Prerequisite: N 03 = YES
O06 L/C Input C1
Range: ALARM
WARNING 1
WARNING 2
Default: ALARM
1. Load cell cable not (or improperly) connected.
2. Analog-to-digital converter of measuring amplifier
is in saturation (see Service Value wz_roh).
3. Supply voltage has fallen below 19V.
Fault must be available for min. 3 s.
O07 No Release S2
Range: WARNING 1
WARNING 2
IGNORE
Default: WARNING 1
RELEASE input signal pending.
Special case:
IGNORE always releases feeder.