O08 L/C Input > MAX H4
Range: ALARM
WARNING 1
WARNING 2
Default: ALARM
Load on load cell exceeds 110 % of the total of load
cell rated capacities (C 04).
Full scale: approx. 115 % with CSD load cells.
O09 L/C Input < MIN L4
Range: ALARM
WARNING 1
WARNING 2
Default: ALARM
Load on load cells is smaller than 3 % of the total of
load cell rated capacities.
O10 Simulation Active S7
Range: WARNING 1
WARNING 2
ALARM
IGNORE
Default:
WARNING 2
Simulation mode started
O11 Error Ext. Event E6
Range: ALARM
WARNING 1
WARNING 2
IGNORE
Default: ALARM
The event E6 is set when the external digital input
(parameter P06) is set.