Block P: Digital Inputs
P01 Release
Range: DI
—
Default: DI (DI1)
Determine digital input for feeder release.
Setting “-” means that no release is required.
Default is DI1, however, any other free digital input
can be used as well.
P02 DI Stop Batch
Range: DI
—
Default: DI (DI3)
Digital input signal used to abort a running batch.
P03 Ackn. Events
Range: DI
—
Default: DI (DI1)
Digital input used to acknowledge event messages.
Level acts statically and should not be permanently
available (permanent acknowledgement).
P04 DI Start
Range: DI
__
Default: —
If OP has been selected for start source, digital input
“DI Start” can be configured and used to start feeder
using a start pulse (key). Feeder is stopped by a pulse
output across digital input “Release”.
This configuration is possible parallel to the
START/STOP keys on INTECONT keyboard.
P05 DI Setting to zero
Range: DI
__
Default: —
The function setting to zero can also be started via the
digital input. The program is started by a positive flank
of the contact. The result is automatically accepted if it
is within the admissible zero setting limit (5% of the
nominal belt load). An ackowledgement of the result is
not necessary. The calibration program can only be
aborted in its active phase.
P06 DI Ext. Event
Range: —
DI
Default: —
Digital input for external fault signals