Block Q: Digital Outputs
Q01 DO Alarm
Range: DO
Default: DO I+DO3 LO
Digital output used to report general alarm.
Q02 DO Prefeeder ON
Range: DO
Default: DO (DO4)
Digital output used to START/STOP prefeeder.
Q03 DO Feeder ON
Range: DO
Default: DO (DO5)
Digital output signal used to indicate START/STOP
state of scale.
This very output can also be used to START/STOP
drive.
Q04 DO I-MIN
Range: DO
Default: Do (DO1)
Digital output signal used to indicate that minimum
feed rate (F01) is exceeded down. Contact output is
independent of event class (F02).
Q05 DO I-MAX
Range: DO
Default: DO (DO2)
Digital output signal used to indicate that maximum
feed rate (F03) is exceeded up.
Contact output is independent of event class (F04).
Q06 DO Q-MIN
Range: DO
Default:
Digital output signal used to indicate that minimum
belt load (F05) is exceeded down.
Contact output is independent of event class (F06).
Q07 DO Q-MAX
Range: DO
Default:
Digital output signal used to indicate that maximum
belt load (F07) is exceeded up.
Contact output is independent of event class (F08).
Q08 DO v-MIN
Range: DO
Default:
Digital output signal used to indicate that minimum
belt speed (F09) is exceeded down.
Contact output is independent of set event class
(F10).
0837
INTECONT PLUS VBW
Parameterization
BV-H2214 GB 77