Q09 DO v-MAX
Range: DO
—
Default: —
Digital output signal used to indicate that maximum
belt speed (F11) is exceeded up.
Contact output is independent of set event class
(F12).
Q10 DO Batch Active
Range: DO
—
Default: —
Digital output signal reporting that a batch is active.
Signal becomes active upon start of batch and is
deactivated when batch is complete. Signal remains
available after abort of batch.
Q11 DO Full Feed
Range: DO
—
Default: DO (DO6)
Full feed signal is available from start of batch until
batch amount “Value for I-MIN (F01)- Batch Dribble
FD (I02)” is reached. Batching continues in dribble
feed.
Q12 DO Dribble Feed
Range: DO
—
Default: DO (DO7)
Dribble feed signal is output after the full feed phase
(see Q11).
Q13 DO Keyboard Mode
Bereich: —
DO
Ur-Wert: —
Digital output signal to report activated keyboard
mode.