7.13
Date Code 20110408 Instruction Manual SEL-551 Relay
Standard Event Reports and SER
Example Standard 15-Cycle Event Report
(Continued from previous page)
[Three cycles of data not shown in this example]
1 0 1 0 2 ............. C0 1........ ..p......... 1...
0 0 -2 -0 -2 ............. C0 1........ ..p......... 1...
0 0 -1 -0 -1 ............. C0 1........ ..p......... 1...
-1 0 -4 -0 -5 ............. C0 1........ ..p......... 1...
-1 0 -1 -0 -2 ............. C0 1........ ..p......... 1...
0 0 2 0 2 ............. C0 1........ ..p......... 1...
0 0 2 0 2 ............. C0 1........ ............ ....
1 0 3 0 4 ............. C0 1........ ............ ....
[One cycle of data not shown in this example]
Event: TRIP Shot: 0 Targets: INST A N
Currents (A Pri), ABCNGQ: 2275 441 482 1 2050 2119
Relay Settings:
RID =FEEDER 1 TID =STATION A
CTR = 120 CTRN = 120 TDURD = 9.000
50P1P = 15.0 50P2P = 20.0 50P3P = OFF 50P4P = OFF
50P5P = OFF 50P6P = OFF 50ABCP= OFF
51P1P = 6.0 51P1C = U3 51P1TD= 3.00 51P1RS= N
51P2P = OFF 51P2C = U3 51P2TD= 15.00 51P2RS= N
50N1P = OFF 50N2P = OFF
51N1P = OFF 51N1C = U3 51N1TD= 15.00 51N1RS= N
50G1P = OFF 50G2P = OFF
51G1P = 1.5 51G1C = U3 51G1TD= 1.50 51G1RS= N
50Q1P = OFF 50Q2P = OFF
51Q1P = OFF 51Q1C = U3 51Q1TD= 15.00 51Q1RS= N
51Q2P = OFF 51Q2C = U3 51Q2TD= 15.00 51Q2RS= N
79OI1 = 30.000 79OI2 = 600.000 79OI3 = 0.000 79OI4 = 0.000
79RSD = 1800.000 79RSLD= 300.000 CFD = 60.000
SV5PU = 12.000 SV5DO = 2.000 SV6PU = 0.000 SV6DO = 0.000
SV7PU = 0.000 SV7DO = 0.000 SV8PU = 0.000 SV8DO = 0.000
SV9PU = 0.000 SV9DO = 0.000 SV10PU= 0.000 SV10DO= 0.000
SV11PU= 0.000 SV11DO= 0.000 SV12PU= 0.000 SV12DO= 0.000
SV13PU= 0.000 SV13DO= 0.000 SV14PU= 0.000 SV14DO= 0.000
NFREQ = 60 PHROT = ABC DATE_F= MDY
SELogic Control Equations:
TR =51P1T + 51G1T + 50P1 * SH0 + LB3
ULTR =!(51P1 + 51G1)
51P1TC=1
51P2TC=1
51N1TC=1
51G1TC=1
51Q1TC=1
51Q2TC=1
52A =IN1
CL =LB4
ULCL =TRIP
79RI =TRIP
79RIS =IN1
79DTL =!LB1 + LB3
79DLS =79LO
79SKP =50P2 * SH0
79STL =TRIP
79BRS =(51P1 + 51G1) * (79RS + 79CY)
79SEQ =0
ER1 =51P1 + 51G1
ER2 =SV5T + CF
SV1 =0
SV2 =0
SV3 =0
SV4 =0
SV5 =TRIP
SV6 =0
SV7 =0
SV8 =0
SV9 =0
SV10 =0
SV11 =0
SV12 =0
SV13 =0
SV14 =0
OUT1 =TRIP
OUT2 =CLOSE
OUT3 =SV5T
(Continued on next page)
OUT4 =0
o
Relay and SEL
OGIC Control
Equations follow the standard
15-cycle event report.