EasyManua.ls Logo

Sel 551 - Coordinating Negative-Sequence Overcurrent Elements

Sel 551
268 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
F.2
SEL-551 Relay Instruction Manual Date Code 20110408
Setting Negative-Sequence Overcurrent Elements
Coordinating Negative-Sequence Overcurrent Elements
To avoid having negative-sequence time-overcurrent elements with such low
time-dial settings trip for this transient negative-sequence current condition,
make settings similar to the following:
SV6PU = 1.500 cycles (minimum response time; transient condition lasts
less than 1.5 cycles)
SV6 = 51Q1 (run pickup of negative-sequence time-overcurrent element
51Q1T through SEL
OGIC Variable timer SV6)
TR = ..+51Q1T*SV6T+.. (trip conditions; SV6T is the output of the
SEL
OGIC Variable timer SV6)
Figure F.1 Minimum Response Time Added to a
Negative-Sequence Time-Overcurrent Element
Continue reading in Coordinating Negative-Sequence Overcurrent Elements
on page F.2 for guidelines on coordinating negative-sequence time-
overcurrent elements and a following coordination example.
Coordinating Negative-Sequence Overcurrent
Elements
The following coordination guidelines and example assume that the negative-
sequence overcurrent elements operate on 3I
2
magnitude negative-sequence
current and that the power system is radial. The negative-sequence overcurrent
elements in the SEL-551 Relay operate on 3I
2
magnitude negative-sequence
current.
The coordination example is a generic example that can be used with any relay
containing negative-sequence overcurrent elements that operate on 3I
2
magnitude negative-sequence current. The SEL-551 can be inserted as the
51Q1T*SV6T
I (3I
2
)51Q1
SV6PU
t

Table of Contents

Related product manuals