8.7
Date Code 20110408 Instruction Manual SEL-551 Relay
Testing and Troubleshooting
Acceptance Testing
=>>SHO <Enter>
Relay Settings:
RID =FEEDER 1 TID =STATION A
CTR = 120 CTRN = 120 TDURD = 9.000
50P1P = 15.0 50P2P = 20.0 50P3P = OFF 50P4P = OFF
50P5P = OFF 50P6P = OFF 50ABCP= OFF
51P1P = 6.0 51P1C = U3 51P1TD= 3.00 51P1RS= N
51P2P = OFF 51P2C = U3 51P2TD= 15.00 51P2RS= N
50N1P = OFF 50N2P = OFF
51N1P = OFF 51N1C = U3 51N1TD= 15.00 51N1RS= N
50G1P = OFF 50G2P = OFF
51G1P = 1.5 51G1C = U3 51G1TD= 1.50 51G1RS= N
50Q1P = OFF 50Q2P = OFF
51Q1P = OFF 51Q1C = U3 51Q1TD= 15.00 51Q1RS= N
51Q2P = OFF 51Q2C = U3 51Q2TD= 15.00 51Q2RS= N
79OI1 = 30.000 79OI2 = 600.000 79OI3 = 0.000 79OI4 = 0.000
79RSD = 1800.000 79RSLD= 300.000 CFD = 60.000
DMTC = 5
PDEMP = 5.00 NDEMP = 1.50 GDEMP = 1.50 QDEMP = 1.50
Press RETURN to continue
SV5PU = 12.000 SV5DO = 2.000 SV6PU = 0.000 SV6DO = 0.000
SV7PU = 0.000 SV7DO = 0.000 SV8PU = 0.000 SV8DO = 0.000
SV9PU = 0.000 SV9DO = 0.000 SV10PU= 0.000 SV10DO= 0.000
SV11PU= 0.000 SV11DO= 0.000 SV12PU= 0.000 SV12DO= 0.000
SV13PU= 0.000 SV13DO= 0.000 SV14PU= 0.000 SV14DO= 0.000
NFREQ = 60 PHROT = ABC DATE_F= MDY
=>>
The SHO Command (Showset) on page 5.16 explains the other settings
available with variations of the SHO command.
Outputs
Step 1. Purpose:
Verify that contact outputs operate when you execute the
PULSE command.
Method:
a. Isolate all circuitry connected to the output contacts.
b. Set the target LEDs to display the contact outputs by
typing TAR 12 <Enter>. The front-panel LEDs should
now follow Row 12 of the Relay Word where the
outputs are listed.
c. Execute the PULSE n command for each output
contact.
d. Verify that the corresponding target LED illuminates
and that the output contact closes for approximately one
second. For example, type PUL OUT1 <Enter> to test
output contact
OUT1.
The response of a programmable alarm output contact
to a PULSE command is discussed in the Output
Contacts on page 3.39.
Inputs
Step 1. Purpose:
Verify that logic inputs assert when control voltage is applied
across the respective terminal pair.
Method:
a. Set the target LEDs to display the contact inputs by
typing TAR 4 <Enter>. The fourth and fifth front-
panel LED should now follow logic inputs IN1 and
IN2, which are in Relay Word Row 4.2.