EasyManua.ls Logo

Sel 551 - Page 191

Sel 551
268 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8.13
Date Code 20110408 Instruction Manual SEL-551 Relay
Testing and Troubleshooting
Acceptance Testing
Phase Overcurrent
Elements
The SEL-551 has many phase overcurrent elements as shown in Table 8.1 and
Table 8.2. Except for elements 50A, 50B, and 50C, they operate based on a
comparison between the maximum phase current directly applied to the phase
inputs and the phase overcurrent setting.
Test the instantaneous and inverse-time phase overcurrent elements by
applying current to the inputs and comparing relay operation to the phase
overcurrent settings. These tests were previously outlined in this section.
Negative-Sequence
Overcurrent Elements
The SEL-551 has four negative-sequence overcurrent elements as shown in
Table 8.1 and Table 8.2. They all operate based on a comparison between a
negative-sequence calculation of the three-phase inputs and the negative-
sequence overcurrent setting. The negative-sequence calculation that is
performed on the three-phase inputs is as follows (assuming ABC rotation):
Equation 8.2
This means that if balanced positive-sequence currents are applied to the relay,
the relay reads 3I2 = 0 (load conditions).
For testing purposes, apply a single-phase current to the relay and the
negative-sequence overcurrent elements will operate. For example, assume
one ampere on A-phase and zero on B- and C-phases:
Equation 8.3
Test the instantaneous and inverse-time negative-sequence overcurrent
elements by applying current to the inputs and comparing relay operation to
the negative-sequence overcurrent settings. These tests were previously
outlined in this section.
Neutral Ground
Overcurrent Elements
The SEL-551 has four neutral ground overcurrent elements. They all operate
based on a comparison between the separate neutral current input (IN) and the
neutral ground overcurrent setting.
For testing purposes, apply a single-phase current to the separate neutral input
and the neutral ground overcurrent elements will operate at the setting
threshold.
Test the instantaneous and time-delayed neutral ground overcurrent elements
by applying current to the inputs and comparing relay operation to the neutral
ground overcurrent settings. These tests were previously outlined in this
section.
Negative-Sequence Level 2 51Q2 2
Pickup 51Q2P (picked up)
Curve 51Q2C
Time-Dial 51Q2TD 51Q2T 2
Electromechanical Reset 51Q2RS (timed out)
Table 8.2 Inverse-Time Overcurrent Elements and Corresponding Settings/
Relay Word Bits/TAR Commands (Sheet 2 of 2)
Element/Settings Setting Names Relay Word Bits TA R
3I2 A-phase B-phase (shifted by –120°)+=
+ C-phase (shifted by 120°)
3I2 1 0 (shifted by –120°)+=
+ 0 (shifted by 120°)
1 (simulated ground fault condition)=

Table of Contents

Related product manuals