EasyManua.ls Logo

Sel 551 - Page 251

Sel 551
268 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
G.15
Date Code 20110408 Instruction Manual SEL-551 Relay
Modbus RTU Communications Protocol
Modbus RTU Communications Protocol
003D +5_REG power
supply status mes-
sage
b
0 = OK,
1 = Warn,
2 = Fail
––
003E –5_REG power
supply value
c
V –600 0 1 0.01
003F –5_REG power
supply status
message
b
0 = OK,
1 = Warn,
2 = Fail
––
0040 +10_ps power supply
value
b
V 0 1500 1 0.01
0041 +10_ps power supply
status message
b
0 = OK,
1 = Warn,
2 = Fail
––
0042 –10_ps power supply
value
c
V –1500 0 1 0.01
0043 –10_ps power supply
status message
b
0 = OK,
1 = Warn,
2 = Fail
––
0044 VBAT power supply
value
b
V 0 500 1 0.01
0045 VBAT power supply
status message
b
0 = OK,
1 = Warn,
2 = Fail
––
0046 TEMP in degrees
Celsius
c
°C 100 100 1 1
0047 Temperature status
b
0 = OK,
1 = Warn,
2 = Fail
––
0048 RAM status
b
0 = OK,
2 = Fail
––
0049 ROM status
b
0 = OK,
2 = Fail
––
004A CR_RAM status
b
0 = OK,
2 = Fail
––
004B EEPROM status
b
0 = OK,
2 = Fail
––
Table G.18 Modbus Map (Sheet 3 of 15)
Address
(Hex)
Field Units
Range
Scale
Factor
Low High Step

Table of Contents