4.9 Line choke
Install the line choke close to the application inverter but outside the minimum clear-
ance for cooling. The line choke must not be heated by the exhaust air of the applica-
tion inverter.
Install the line choke before the line filter.
The connection cable between line choke and line filter does not have to be shiel-
ded.
Limit the length of the cable between the line choke and the line filter to the abso-
lute minimum needed.
4.10 Line filter
Install the line filter close to the application inverter but outside the minimum clear-
ance for cooling. The line filter must not be heated by the exhaust air of the appli-
cation inverter.
Do not wire any other consumers between the line filter and the application in-
verter.
The connection cable between line filter and application inverter does not have to
be shielded.
Limit the length of the cable between the line filter and the application inverter to
the absolute minimum needed.
Do not switch between the NF... line filter and inverter.