EasyManua.ls Logo

SEW-Eurodrive MOVIDRIVE MDA90A-0160-503-X-S00

SEW-Eurodrive MOVIDRIVE MDA90A-0160-503-X-S00
288 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9
Functional safety
Safety Conditions
Operating Instructions – MOVIDRIVE
®
modular
256
9.3.3 Requirements on the external safety controller
A safety relay can be used as an alternative to a safety controller. The following re-
quirements apply analogously.
The safety controller and all other safety-related subsystems must be approved for
at least that safety class which is required in the overall system for the respective,
application-related drive safety function.
The following table shows an example of the required safety class of the safety
controller:
Application Safety controller requirements
Performance level d according to
ENISO13849-1, SIL 2 according to
EN62062
Performance Leveld according to
ENISO13849-1, SIL 2 according to
EN61508
Performance level e according to
ENISO13849-1, SIL 3 according to
EN62061
Performance level e according to
ENISO13849-1, SIL 3 according to
EN61508
The wiring of the safety controller must be suitable for the required safety class,
(see manufacturer documentation). The STO input of the application inverter can
be switched with 2 poles (sourcing output, sourcing/sinking, or serial sourcing) or
with 1 pole (sourcing).
The values specified for the safety controller must be strictly adhered to when
designing the circuit.
Electro-sensitive protective equipment (such as light grid or scanner) according to
EN 61496‑1 and emergency stop buttons must not be directly connected to the
STO input. The connection must be realized using safety relays, safety controllers
etc.
To ensure protection against unintended restart in accordance with EN1037, the
safe control system must be designed and connected in such a way that resetting
the command device alone does not lead to a restart. A restart may only be carried
out after a manual reset of the safety circuit.
If no fault exclusion is used for the STO wiring according to ENISO13849‑2 or
DINEN61800‑5‑2, the external safety device must detect the following faults in
the STO wiring within 20s depending on the connection type:
2-pole sourcing:
Short circuit of 24V at F_STO_P1 or F_STO_P2 (Stuck-at 1)
Crossfault between F_STO_P1 and F_STO_P2
2-pole sourcing/sinking:
Short circuit of 24V at F_STO_P1 (Stuck-at 1)
Short circuit of 0V at F_STO_M (Stuck-at 0)
2-pole serial sourcing:
Fault exclusion is mandatory
1-pole sourcing:
Short circuit of 24V at F_STO_P (Stuck-at 1)
2-pole sourcing:
In disconnected state, no switch-on test pulses must occur in the sourcing cables.
In connected state:
24748536/EN – 11/2017

Table of Contents

Related product manuals