4
Installation
Electrical installation
Operating Instructions – MOVIDRIVE
®
modular
81
4.6.7 24V supply voltage
MOVIDRIVE
®
modular requires an external 24V supply voltage. Us the following in-
stallation material for the connection:
• M4 fork-type or ring lugs with insulating collar and a cable cross section of max-
imum 4mm
2
,
or
• M4 tubular cable lugs with insulating heat shrink tubing and a cable cross section
of maximum 6mm
2
.
14476866443
Select the cross section of the supply cable according to the power demand of the
device to be supplied. Note the additionally required power of the directly supplied
24V brake for CMP motors with BK or BP brake without brake control.
The maximally permitted length of the 24V supply cable is 30m.
24748536/EN – 11/2017