Installation
108/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
Isolate and earth the busbar.
Verify safe isolation from supply.
Remove the low-voltage plug connector at the voltage transformer.
Remove the cover of the voltage transformer.
Remove the fixing bolts of the adapter plate.
Screw four press-out bolts into the holes provided for this purpose in the adapter plate.
Press the voltage transformer out of the bushing together with the adapter plate with
the help of the press-out bolts. While doing so, screw the press-out bolts in uniformly,
so that the transformer is not canted.
Fixing bolts at
the adapter plate
Holes with setnut for
press-out bolts
ATTENTION
Risk of injury! While being removed from the bushing, the voltage transformer can detach
suddenly.
Remove the voltage transformer upwards as uniformly as possible.
Do not use excessive force.
ATTENTION
Risk of injury! The voltage transformer type 4MT3 has a weight of approx. 30 kg.
Secure the voltage transformer against falling down.
If necessary, transport the voltage transformer with several persons or with suitable aids.