EasyManua.ls Logo

Siemens 8DB10 - Opening the Three-Position Disconnector Manually; Activating the Ready-To-Earth Function Manually

Siemens 8DB10
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 155/214
Operation
37.3 Opening the three-position disconnector manually
Pre-select busbar system for switching operation.
Selector gate to the left: Busbar system 1. Selector gate to the right: Busbar system 2.
Push the left-hand control gate to the left.
The opening for the DISCONNECTING function is free.
Switch the three-position disconnector to OPEN position (insert the operating lever for
the DISCONNECTING function and turn 180° counter-clockwise).
The three-position disconnector is open.
The position indicator changes to OPEN position.
Remove the operating lever for the DISCONNECTING function.
The left-hand control gate returns to its initial position.
The opening for the DISCONNECTING function is closed.
37.4 Activating the ready-to-earth function manually
Fig. 179: Opening the three-position disconnector
ATTENTION
In circuit-breaker panels, a mechanical interlock prevents the three-position disconnector from
being operated when the circuit-breaker is closed.
Open the circuit-breaker (see page 148, "Opening the circuit-breaker manually").
ATTENTION
In disconnector panels without electromechanical/mechanical interlock, maloperation of the
three-position disconnector is possible. Here, the three-position disconnector can be operated
under load. Operating under load will destroy the three-position disconnector!
Do not operate the three-position disconnector under load.