Installation
96/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
26 Installing voltage transformers
DANGER
The voltage transformer can explode!
If the voltage transformer is short-circuited, there is risk of explosion!
Check the voltage transformer circuits up to the m.c.b. or the fuse for short-circuits.
DANGER
High voltage! Danger! Before starting installation work at the voltage transformers, the busbar
must have been isolated and earthed.
Isolate and earth the busbar.
Verify safe isolation from supply.
ATTENTION
Sensitive parts of the switchgear may be damaged during installation work at the busbar and
the busbar housings.
While working at the busbars or the busbar housings, prop up only on the aluminum
housings and the frame.
Do not prop up on sensitive parts of the switchgear like gas pipes, bursting discs, shafts,
etc.
ATTENTION
While working on metal-coated voltage transformers, the coating may be scratched or
damaged. Then, the voltage transformers cannot be touched anymore.
Work carefully while mounting metal-coated voltage transformers.
Take care not to scratch or damage the metal coating.
ATTENTION
Risk of partial discharges at the voltage transformer bushings due to pollution.
Clean all bushings at the panel at the voltage transformer carefully before starting
installation work.
Observe extreme cleanliness while working.