Operation
166/214 Revision 06 INSTALLATION AND OPERATING INSTRUCTIONS 8DB10 864-5091.9
38 Feeder earthing and de-earthing
DANGER
High voltage! Danger! Do always observe the Five Safety Rules
Isolate the switchgear.
Secure against reclosing.
Verify safe isolation from supply.
Earth and short-circuit.
Cover or barrier adjacent live parts.
DANGER
Danger! High voltage! The earthing process is not completed until the circuit-breaker is closed.
Close the circuit-breaker after having switched the three-position disconnector to READY-
TO-EARTH position.
ATTENTION
Earthing under load will destroy the three-position disconnector.
For circuit-breaker panels: Circuit-breaker panels cannot be operated when the
disconnecting function is mechanically interlocked (see page 148, "Opening the circuit-
breaker manually").
For disconnector panels: Make sure that the feeder is isolated from supply.