864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06 131/214
Installation
30 Final installation work
30.1 Mounting cables with plugs
Proceed according to the installation instructions of the corresponding plug manufacturer.
Mount the cable bracket (option). Distance between lower edge of panel connection
housing and cable bracket: Minimum 450 mm.
30.2 Connecting low-voltage cables
Connect low-voltage cables of customer (option):
Remove the metal covers from the frames.
Open the doors of the low-voltage compartments.
Fix the low-voltage cables at the holders provided for this purpose.
Connect the ends of the cables to the terminals in the low-voltage compartment according
to the circuit diagram.
Close the doors of the low-voltage compartments.
ATTENTION
The dust-proof caps supplied on the sockets of the multiple panel connections do not provide
sufficient shock protection.
Close unused sockets of multiple panel connections with dummy plugs.
ATTENTION
Do not bolt cable shields onto panel connection housings in order to avoid damage to the
switchgear.
Connect cable shields to the cable bracket or to the switchgear earth.
Fig. 144: Fixing of low-voltage cables
Fixing of low-voltage cables at the upper front support
Fixing of low-voltage cables at the lower front support
Low-voltage cables